AC High Voltage Low Capacity Test Sets for Testing Insulators



AC High Voltage Low capacity testers are  specially designed for testing Insulators, CT’s PT’s, Low dielectric capacitive electrical equipment, transformers etc. as per National and International  Standards.  During  manufacturing each unit is tested at multiple stages, thus ensuring consistency and best  quality. These instruments are air cooled, oil cooled or air & oil cooled combined as per design. The units have been manufactured up to 800kV and up to 200kVA.The units have type of tests such as dry withstand, wet withstand, breakdown voltage in air/oil, oil insulation, and pollution Test.

AC High Voltage Low Capacity Test Set
Sr. No.
Parameters
Description
1
I/p Voltage 
220/230V or 380/400V, 50 or 60HZ AC supply
2
O/p Voltage
Up 800KV and 250mA
3
Capacity
Up  to 200KVA
4
Timer
0-9999 Sec./min. Digital
5
Control
Type 1- The unit can be manual/motorized control for voltage variation and push button controlled for HT actuation.
Type  2- The unit can be complete with on board digitized panel with or without computer connectivity.
Type  3- The unit can be PLC based complete with computer, HMI memory, printer etc. for operation.
6
Metering
Voltmeter : One Digital type connected on HT side to indicate the output voltage
Scale :  0-800 kV AC.
Ammeter : One Digital type ammeter Connected on earth side to indicate the leakage Current on sample under test.
Scale :  0-500mA
Applicable only for type -1
For type -2 and type 3 metering is self contained
7
Protection 
Tripping   -  A fast acting DC relay will isolate the circuit when the current exceeds pre-set level.
Overload  - This is used as a  secondary protection  in case the input loads exceeds the preset value
Overvoltage -  This is used as a  secondary protection  in case the output voltage exceeds the preset value
8
Interlocking
Zero Start Interlock  -  The unit will have zero start interlocking to avoid the transients on HV transformer and provision for  cage door interlocking shall also be provided.
Earth interlock- It ensures that HV will not actutae untill good earthing is not provided.
9
Termination
The HT output on suitable HT insulator and other point at earth potential will be brought out on suitable insulator
10
Control Panel
The control panel is designed for five unique purposes.
1 -Control
2- Measure
3- Protect (Active and Passive)
4- Tripping
5 -Annunciate   
11
HV Transformer

The transformers are designed and manufactured as per IS /IEC guidelines. Single /  Multiple stage stepup transformers are utilized  for achiving the desired voltage. The units are designed and manufactured using the  preeminent material from India and Abroad. The coils are vacuum impregnated and insulated with High Quality EHV Grade transformer oil as per relevant IS and IEC Standard.



For further details or requirements, Email us

AC High Voltage HV Testers for Testing Transformers


AC High Voltage High capacity testers are  specially designed for testing cables, Generators, transformers and other high capacitive equipments as per National and International  Standards. During  manufacturing each unit is tested at multiple stages, thus ensuring consistency and best  quality. These instruments are air cooled, oil cooled or air & oil cooled combined as per design. The units have been manufactured up to 800kV and up to 3000kVA.The units have type of tests such as dry withstand, wet withstand, breakdown voltage in air/oil, oil insulation, and pollution Test.

Features:

  • Light in weight
  • Casted Wheel for easy movement
  • Multiple safety locks for the operator
  • Specially designed for field operation.


Standard Accessories:
  • Interconnecting Control Cable.
  • Discharge Rod.
  • Audio Visual alarm indicator.
  • Corona Shield


Optional Accessories:

  • Output HV cable.
  • Interconnecting / input power cable.
  • Earthling lead.
  • Canvas cover.
  • LV Transformer Oil.


For further details or requirements, Email us

High Voltage High Capacity Testers for Testing Generators


AC High Voltage High capacity testers are  specially designed for testing cables, Generators, transformers and other high capacitive equipments as per National and International  Standards. During  manufacturing each unit is tested at multiple stages, thus ensuring consistency and best  quality. These instruments are air cooled, oil cooled or air & oil cooled combined as per design. The units have been manufactured up to 800kV and up to 3000kVA.The units have type of tests such as dry withstand, wet withstand, breakdown voltage in air/oil, oil insulation, and pollution Test.

For further details or requirements, Email us

AC HV Rubber Testing Set for Testing Rubber Mats


‘RE’ AC HV Rubber testing set is used for Testing Rubber Mats. These sets are generally used in Electrical manufacturing Industry/Power Houses, Electrical Repair etc. where AC H.V. test set is suggest by BIS or IEC. During AC H.V. testing High current is generated due to capacitive loading. AC High voltage test equipments are designed for continuous use, for testing, and can withstand short circuit. Fault burning can also be provided if desired.


AC High Voltage Insulation Test Set
Sr. No.
Parameters
Description
1
I/p Voltage 
220/230V or 380/400V, 50/60HZ AC supply
2
O/p Voltage
Up 60KV and 100mA
3
Capacity
Up  to 6KVA
4
Timer
0-9999 Sec./min. Digital
5
Control
1- The unit can be manual/motorized control for voltage variation and push button controlled for HT actuation.
2-Selectror switch to select leakage current at 25%,50%,75% and 100% of the mA capacity required.
3- The unit can be microprocessor based complete with on board memory, printout facility, programmable features etc.
4- The unit can be PLC based complte with computer, HMI memory, printer etc. for operation.
6
Metering
Voltmeter : One Digital type connected on HT side to indicate the output voltage
Scale :  0-60 kV AC.
Ammeter : One Digital type ammeter Connected on earth side to indicate the leakage Current on sample under test.
Scale :  0-100mA 
7
Protection 
A fast acting DC relay will isolate the circuit when the current exceeds pre-set level.
8
Interlocking
The unit will have zero start interlocking to avoid the transients on HV transformer and provision for  cage door interlocking shall also be provided
9
Construction
AC High voltage test set consists of
1) Control panel cum Regulating Transformer cum High Voltage Transformer.
9(a)
Control Panel

Consist of :
LT ON Indicator , Push button to actuate HT, HT ON Indicator,Push button to deactuate HT, Fault Indicator (HT OFF Indicator), Push Button Switch to increase / decrease the output voltage, Tripping selector switch with tripping @ 10-15-20-25-30-35-40-50-60-70-80-90-100mA, Timer ON/OFF Switch, Switch for rate of rise @ 0.5kV/sec and 2kV/sec,  Timer Digital, Digital KV Meter, Digital mA Meter
9(b)
Regulating Transformer
Continuously variable transformer which feeds 0-230 V, to the main HV transformer. The voltage is boosted in ratio with transformer design. No wave shape distortion will take place. One terminal of HT transformer is maintained at earth potential through CST terminal, the other Ht terminal is brought out on suitable H.T. Load.
Protection:  The protective circuit incorporated in this unit consist of the following :
A) Zero Start Interlocking
B) Over current relay with current selection
C) Cage door at top side
This prevents accidental start of unit after break down.
9(c)
HV Transformer
The Main step up transformer is housed inside the body  supported with welded angle iron frame and the output has been brought out through  H.T.  Terminal.



For further details or requirements, Email us